Fire Detecting Systems

Specification

  • Length: cm 0
  • Width: cm 0
  • Height: cm 0
  • Volume: cc 0
  • Weight: kg

Availability: In stock

Delivery Time: 2-3 Tage

OR
Art.Nr.: SEE808393

Hardware FlexES Control FX10 basic configuration, with software support for 5 loops

Hardware FlexES Control FX10 basic configuration, with software support for 5 loops.

Features:

Combinable loop/spur technology with decentralized
intelligence
Freely configurable functionality of modules
4 free programmable potential free contacts and 1
output for alarm transmission unit (ATU)
Increased availability via emergency mode function
of the loop modules
Emergency mode for monitored areas up to
48,000 m² or more than 512 fire detectors acc. to
the German Planning standard VDE 0833 and/or
VdS 2095.
USB, Ethernet, RS 485, TTY interfaces onboard
Direct output of the proprietary EDP communications
protocol (Data Protocol) via interface RS
485
Operation of loop-powered alarm signaling
devices (optical/acoustic/voice) in different alarm
zones via esserbus-PLus
Cascadable power supply to 450 W according to
EN 54-4
Loop length up to 3.5 km (esserbus)
Operation of different input/output gateways
Integrated interfaces for operation of required fire
brigade periphery, e.g. fire brigade indicating
panel, fire brigade operating unit
Event memory with 10,000 entries
Operation of VdS-approved wireless components
with convenient field intensity measurement
Parameterization, calibration and programming
directly via USB
Galvanic isolation of analog loops possible