Smoke switch ORS 142
Optical smoke detector for smoldering fires and open fires with smoke development.
attributes:
- Revision display according to DIN 14677
- Pollution Compensation
- Optical Verschmutzungs-/Zustandsanzeige
- Measuring chamber monitoring
- Communication port for RSBUS
- Potential-free NC contact
- Thermocouple to trigger at an ambient temperature above 70 ° C
- With dust cap
Smoke detection in accordance with EN54, Part 7
Temperature: 70 ° C
Operating voltage: 18 to 28 V DC
Current consumption at 28 V DC
Quietness: 22 mA
Alert: 11 mA
Disorder: 16 mA
Relay contact: NC
Switching voltage 30 V DC
Switching current: 1 A
Switching power: 30 W
Degree of protection: IP 42
Operating ambient temperature: -20 ° C - +60 ° C
Color: white, similar to RAL 9010